Services - Separate IT and OT with a boundary your operations can live with
Many OT networks grew around the project that built them. A flat network, a shared firewall or one server with a foot on each side can leave a corporate compromise a short path to control systems.
I design IT/OT segmentation that fits how your operations really run: Purdue model levels, zones and conduits, a DMZ between corporate and control networks, and a staged path to get there.
Why OT segmentation is not a VLAN project
The tools are familiar to any network team. What changes is the cost of a wrong rule.
- A wrong rule can stop operations. A blocked flow on a corporate network raises a help desk ticket. A blocked flow between a control system and its server can interrupt a live process, so each change needs a maintenance window and a way back.
- The boundary replaces missing host controls. Controllers and older HMIs often cannot run endpoint protection or take a routine patch. The zone boundary has to carry controls that IT would normally place on the host.
- The Purdue model is a map, not a design. It shows functional levels. It does not show which assets share a consequence, and virtualisation and cloud services blur the levels. Grouping assets by their security requirements is the step that turns the map into a design.
- Neither team can own the rules alone. Network engineers understand the firewall. Control systems engineers understand the process behind each flow. Rules that only one side owns drift, and the boundary weakens with no one watching it.
What the design covers
You receive a written design: the zone and conduit model, a register of every permitted flow, the boundary requirements and a staged plan.
- Scope and flows. The system under consideration, including the IT networks that serve the process. Each flow recorded by source, destination, protocol, direction and business reason.
- Zones. Assets grouped by security requirements and by the consequence of losing them, mapped to your Purdue model levels, with a target security level for each zone.
- Conduits. Every path between zones defined as a conduit, with its protocols and its direction of data flow. Flows that nobody can justify come out.
- The IT/OT DMZ. No direct flows between corporate and control networks. Historians, data servers and jump hosts sit in a screened zone, so IT reads data there and not from the control network.
- Firewall design. One firewall with a DMZ or a paired design, chosen by consequence. Default deny, rules written to host level, and outbound rules as strict as inbound.
- Who can change the boundary. Firewall management kept apart from both networks, joint ownership of the rules, and change control that follows your maintenance windows.
- Paths that skip the network. Removable media and other routes that cross a zone boundary without using a conduit, with the procedural and physical controls that cover them.
- Monitoring. Sensors placed at zone boundaries, because a sensor sees only the traffic that reaches it, and alerts on any flow outside the register. Detection adds to blocking controls and does not replace them.
- Staged cutover. A sequence of changes that fits your maintenance windows, with testing where a test environment exists and a way back at each step.
One boundary, three owners
The same design has to work for each side of it.
- If you run the IT side. You get a flow register and a rule design you can defend in an audit, with a plain account of why some OT assets cannot follow your standard policy and what compensates for that.
- If you run the OT side. You get a design that starts from what the process needs. Each rule is checked by someone who knows that process, and nothing cuts over outside your window.
- If you deliver the project. You get an independent view of the design before commissioning, and zones and conduits that line up with ISA/IEC 62443.
Where this meets your obligations
The AESCSF treats the separation of IT and OT as a basic architecture practice, and later practices in the same progression ask for more. ISA/IEC 62443 gives the zone and conduit model and the risk assessment behind it. For a responsible entity under the SOCI Act, the design also supports your risk management program. The work follows the joint secure connectivity principles for OT.
Connecting to the cloud as well? See what I check before go-live.
Who does the design
I spent ten years at Sydney Light Rail, ending as Operational Technology Manager, accountable for SCADA, control room and communications systems. As a consultant I have designed Purdue model segmentation and zone and conduit architectures across SCADA and DCS environments. I hold the CISSP and the ISA/IEC 62443 Cybersecurity Expert certificate, so I can read the design from both sides of the boundary.
Planning to segment IT and OT?
Location
- Sydney, Australia
On site and remote across Australia
ABN 30 299 011 778